Home Page Company Profile Our Products
BRIGHT STAR AIRCON
 
Home » Products » Refrigeration & Air Conditioning Equipment » Cold Room

Cold Room



Cold Room   Next >>

Product Code : 05

Product Specification

Cold Rooms:

Our cold rooms  are sturdy and robust in structure. They are made up of thick foam impact panels that provide insulation to the structure. Moreover, they have flexible or swing doors that facilitate easy putting in or taking out of material.

Features:

  • Employs latest technology.
  • Easy to use and to clean.
  • Standard aluminum hood and track.
  • Removable galvanized steel.
  • Negligible maintenance.

For the general purpose cold store, involving meats, vegetables and dairy products, it is common procedure to balance the unit cooler to the condensing unit at a 5.5 to 6.6oC (10 to 12oF) TD.
If this is done then from experience one can expect to maintain in a 1.7oC (35oF) room a 80 to 85 % relative humidity which is good range for general storage.
In a freezer room where the product is stored below 0oC (32oF) all moisture is in the form of ice or frost; the product is frozen solid and therefore a 5.5oC (10oC) TD is satisfactory for all products.

TECHNICAL DATA OF UNITS FOR SMALL AND MEDIUM COLD ROOMS FOR AN INSIDE TEMP RANGE OF (-4 Deg.C to 6 Deg.C) REFRIGERANT USED R-22, R-134a, R-404a
MODEL BSC -0.6 BSC-0.75 BSC-1.0 BSC-1.25 BSC-1.5 BSC-2.0 BSC-2.5 BSC-2.75
TONS OF REF. 0.6 0.75 1.0 1.25 1.5 2 2.5 2.75
COLD ROOM OF EXTERNAL SIZE IN METRES 2.5 x 2.5 x 2.4 3.5 X 2.5 X 2.4 3.5 X 3.5 X 3.0 4.0 X 4.0 X 3.0 5.0 X 4.0 X 3.0 6.0 X 4.5 X 3.0 6.0 X 5.5 X 3.0 7.0 X 6.5 X 3.0
AVERAGE POWER CONSUMPTION FOR R 22 0.75 KWH 1.05 KWH 1.20 KWH 1.45 KWH 1.85 KWH 2.35 KWH 2.80 KWH 3.25 KWH
AVERAGE POWER CONSUMPTION FOR R-134a 0.65 KWH 0.80 KWH 1.05 KWH 1.25 KWH 1.40 KWH 2.10 KWH 2.30 KWH 2.75 KWH
AVERAGE POWER CONSUMPTION FOR R 404A 0.75 KWH 1.05 KWH 1.30 KWH 1.55 KWH 1.95 KWH 2.50 KWH 2.90 KWH 3.35 KWH

Note: 1) The above units are rated at (+) 2 Deg. C Inside Room Temp.
2) We can also deisgn the unit as per our customers' requirement.

TECHNICAL DATA OF UNITS FOR SMALL AND MEDIUM COLD ROOMS FOR AN INSIDE TEMP RANGE OF (-5 Deg.C to -20 Deg.C) REFRIGERANT USED R-404a
MODEL BSC -0.5 BSC-0.75 BSC-1.0 BSC-1.25 BSC-1.5> BSC-1.65 BSC-1.8 BSC-2.0
TONS OF REF. 0.5 0.75 1.0 1.25 1.5 1.65 1.8 2.0
COLD ROOM OF EXTERNAL SIZE IN METRES 2.5 x 2.5 x 2.4 3.5 X 2.5 X 2.4 3.5 X 3.5 X 3.0 4.0 X 4.0 X 3.0 5.0 X 4.0 X 3.0 6.0 X 4.5 X 3.0 6.0 X 5.5 X 3.0 7.0 X 6.5 X 3.0
AVERAGE POWER CONSUMPTION FOR R-404a 1.45 KWH 2.45 KWH 2.85 KWH 3.40 KWH 4.50 KWH 5.00 KWH 5.50 KWH 6.10 KWH

Note: 1) The above units are rated at (-)20 Deg. C Inside Room Temp.
Other Products in 'Refrigeration & Air Conditioning Equipment' category
Double Skin Evaporating Cooling Unit
Double Skin Evaporating Cooling Unit
Hinges Door For Cold Rooms
Hinges Door For Cold Rooms
Cold Room Sliding Doors
Cold Room Sliding Doors
Fan Coil Unit
Fan Coil Unit
PUF Slabs
PUF Slabs
Air washer (Cooling Unit)
Air washer (Cooling Unit)
 
<< Back


 
 
 

 
Contact Details
BRIGHT STAR AIRCON
UG-7, Usha Kiran Building, Near Akash Cinema, Azad Pur, Delhi - 110033, India
Phone:91-11-32910516/27678955
Fax:91-11-27678955
Send Mail   Send SMS   
Key Personnel
Mr. Sabir Ahmad (Managing Director)
Mobile:+919818774873, +919999648530